SNC-1500R UPS SMART NET CLAIRE Series

SNC-1500R UPS SMART NET CLAIRE Series

Category: Koss

Specifications
Details

  • Pure Sine Wave Output
  • DSP Digital Control
  • Boost and Buck AVR for Voltage Stabilization
  • Auto Sensing Frequency
  • Adjustable Charging Current and Battery Shutdown Point
  • Settable ECO Mode and No-load Shutdown
  • Humanized Alarm System
  • Power-on Self Test
  • Cold Start
  • Auto Restart When Mains Power is Restored
  • Intelligent Battery Management
  • Short Circuit and Overload Protection
  • Automatic Charging in Off Mode
  • USB & RJ45, AS400 / SNMP (optional)
    Communication Port
SNC-1500R UPS SMART NET CLAIRE Series  
MODEL SNC-1500R
Capacity 1500VA/1200W
DC INPUT  
Rated voltage 24V
DC input range(default) 20~30V
AC INPUT  
AC input range(bypass mode) 0~121/132/138/144 Vac for 100/110/115/120Vac ± 10 Vac
  0~242/264/276/288 Vac for 200/220/230/240 Vac ± 10 Vac
AC input range(mains mode) 100V:70~130Vac 110V:80~14Vac 115V:85~145Vac 120V:90~150Vac
  200V:145~260Vac 220V:165~280Vac 230V:175~290Vac 240V:185~300Vac
Frequency input range 50/60Hz (auto-sensing),50/60Hz ± 5%~15%
Generator connection Available(generator input power is settable)
OUTPUT  
Inverter output range 100/110/115/120/200/220/230/240 Vac ± 5% (settable)
AC output range(bypass mode) 0~121/132/138/144 Vac for 100/110/115/120 Vac ± 10 Vac
  0~242/264/276/288 Vac for 200/220/230V/240 Vac ± 10 Vac
AC output range(mains mode) 100V:90~110Vac 110V:99~121Vac 115V:103~126Vac 120V:108~132Vac
  200V:166~226Vac 220V:188~245Vac 230V:199~254Vac 240V:210~264Vac
Output frequency 50/60 Hz ± 0.3Hz (settable)
Waveform Pure sine wave
Inverter efficiency Max. 80%
Energy saving mode Settable(<3%load), enter in 80s
No-load shutdown Settable(<3%load), shut down in 80s
Transfer time ≤10ms
THDV(resistive load) ≤5%
Protections Overload,short circuit(inverter),battery low voltage,battery overcharge,overtemperature
Overload(mains mode) 110% for 120s,125% for 60s,150% for 10s (transfer to bypass mode)
Overload(inverter mode) 110% for 60s,125% for 10s,150% for 5s (shut down directly)
Mute Automatic mute in 60s or by manual
BATTERIES  
Inbuilt battery(standard model) 12V/9Ah×2
Charging current Standard model(S):1 A(default)
  Long time model(H):10A(default);<10A,set step 1A;?10A,set step 5A
Equalizing charge voltage Single battery 14.1 Vdc(default),13.6~15Vdc adjustable
Floating charge voltage Single battery 13.5 Vdc(default),13.2~14.6Vdc adjustable
Low voltage alarm point Single battery 10.8 Vdc(default),9.6~13Vdc adjustable
Low voltage shutdown point Single battery 10.2 Vdc(default),9.6~11.5Vdc adjustable
OTHERS  
Communications USB & RJ45(standard),dry contacts/SNMP(optional)
Operating Temperature 5°C~40°C
Operating humidity Relative humidity≤93%
Noise level ≤50dB(1m)
Rack-mount  
Dimensions(W×D×H)(mm) 440×410×132(S)
Packaged dimensions(W×D×H)(mm) 611×505×235(S)
Net weight(kg) 17.2(S)
Gross weught(kg) 20.4(S)